SIRIUS 3SK1 Expansion Module_x000D_
The 3SK1 output expansion units are used to expand the enabling circuits. The maximum Performance Level PL / Cat. in accordance with ISO 13849-1, SILCL in accordance with IEC 62061, SIL in accordance with IEC 61508 corresponds to the Performance Level PL and SIL of the basic unit when the connection between basic unit and output expansion is configured as fail safe (e.g. basic unit and output expansion are connected using 3ZY12 device connector ). The output expansions can be activated via the supply voltage (A1/A2) or using 3ZY device connectors._x000D_
The operating state of the 3SK1 output expansions is displayed on the LED. The output expansions 3SK1211(4RO) have four safety related enabling circuits as NO circuits, and the output expansions 3SK1213 (3RO) have three. They each have one positively driven NC circuit. The output expansions can be activated via any enabling circuit / output of the basic unit via (A1). The NC circuit 51/52 of 3SK1211 (4RO) or 41/42 of 3SK1213 (3RO) is used for monitoring the output expansions. In the 24 V DC variants, the expansion units can be activated and evaluated via the 3ZY device connectors._x000D_
Output expansion 3SK1211_x000D_
Slide switch for selecting the activation type (time delayed / instantaneous - for 24 Vdc variant only)_x000D_
1 LED for status display_x000D_
4 enabling circuits (safe circuits, NO contacts)_x000D_
1 NC circuit as feedback contact for output expansion 3SK1211 to the up-circuit basic unit_x000D_
Enclosure width 22.5 mm_x000D_
Removable terminals_x000D_
Output expansion 3SK1213_x000D_
Slide switch for selecting the activation type (time delayed / instantaneous - for 24 Vdc variant only)_x000D_
1 LED for status display_x000D_
3 enabling circuits (safe circuits, NO contacts)_x000D_
1 NC circuit as feedback contact for output expansion 3SK1213 for the up-circuit basic unit_x000D_
Enclosure width 90 mm_x000D_
Removable terminals_x000D_
Note_x000D_
When using the 3ZY connector you can switch between instantaneous or delayed control of the basic unit using the slide switch of the output expansion, but when using conventional wiring the slide switch has no function._x000D_
Siemens Output Module For Use With SIRIUS 3SK1, LED Display - SIRIUS Series - 3SK1211-1BB40_x000D_
Expand the number of devices that can be connected to a safety relay with this output module from Siemens. It comes with six outputs, meaning it can simultaneously send signals to multiple applications, ensuring reliable productivity. A wide operating temperature range of -25°C to +60°C makes the unit a safe option for use in demanding conditions. Thanks to an IP20 rating, you can be sure it's safe to touch, as well as being resistant to dust and objects larger than 12mm. For easy compatibility, this module is designed for use with safety relays in the SIRIUS 3SK1 series._x000D_
Single LED status indicator for easy monitoring and diagnostics_x000D_
DIN rail mounting style makes it quick and simple to install_x000D_
Supply of 24V DC is suitable for low-voltage applications_x000D_
Low power loss of 2.5W for energy-efficiency_x000D_
Mechanical service life of 10,000,000 cycles for long-term performance_x000D_
What's size is this output module?_x000D_
This module has compact dimensions of 121.7 (L) x 22.5 (W) x 100mm (H), making it a practical choice for installation in systems where space is limited.