These contactors, unlike relays, are specifically designed to connect to high current load devices. Used in larger-scale applications, Schneider Electrics contactors can be controlled remotely, specifically designed to switch a large amount of electrical power through its contacts._x000D_
These contractors feature varied switching voltages, many of the range feature screw clamp or a solder termination._x000D_
Highly reliable_x000D_
Excellent quality_x000D_
Easily installed accessories_x000D_
What does the utilisation category AC1 and AC3 mean for the TeSys contactors?_x000D_
Contactor utilisation categories define the current making and breaking values, based on the type of load to be controlled and the operating cycle conditions._x000D_
AC-1: This applies to all AC devices with a power factor of at least 0.95. Example of use: resistive load, heating, distribution._x000D_
AC-3: This applies to squirrel cage motors where breaking occurs while the motor is running. Example of use: all squirrel cage motors, lifts, escalators, conveyors, bucket elevators, compressors, pumps, mixers, air conditioning units._x000D_
What accessories are available?_x000D_
Auxiliary contact blocks with serrated wiping action_x000D_
Front mount dust tight auxiliary contact blocks_x000D_
Pneumatic time delay blocks_x000D_
Transient voltage surge suppressors_x000D_
Interface modules and electronic timers_x000D_
Mechanical latching blocks_x000D_
Approvals_x000D_
CSA, UL, NEMKO, DEMKO, SEMKO, FIMKO_x000D_
Standards_x000D_
BS5424 Part 1/IEC 947, VDE 0660, NFC63 110_x000D_
LC1K09105E7 TeSys K Contactor._x000D_
Motor control, Resistive load applications._x000D_
AC-3, AC-1, AC-4 Category._x000D_
[Ie] rated operational current 20 A (at <= 440 V AC AC-1 for power circuit, 9 A at <= 440 V AC AC-3 for power circuit, 16 A (at <70°C) at 690 V AC AC-1 for power circuit._x000D_
Control circuit type AC at 50/60 Hz._x000D_
[Uc] control circuit voltage 48 V AC 50/60 Hz._x000D_
1 NO Auxiliary contact._x000D_
Category III._x000D_
Rated breaking capacity, 110 A at 415 V conforming to IEC 60947, 110 A at 440 V conforming to IEC 60947, 80 A at 500 V conforming to IEC 60947, 110 A at 220...230 V conforming to IEC 60947, 110 A at 380...400 V conforming to IEC 60947, 70 A at 660...690 V conforming to IEC 60947._x000D_
Shock resistant to IEC 60068-2-27._x000D_
Vibration resistant to IEC 60068-2-6._x000D_
Flame resistant V1 conforming to UL 94, Requirement 2 conforming to NF F 16-101, Requirement 2 conforming to NF F 16-102._x000D_
Safety level B10d = 1369863 cycles contactor with nominal load conforming- to EN/ISO 13849-1, B10d = 20000000 cycles contactor with mechanical load conforming- to EN/ISO 13849-1._x000D_
Approvals_x000D_
UL, CSA.