Работаем с юридическими лицами, бюджетными организациями, ИП
По вопросам приобретения товара пишите на info@west-cs.ru
Schneider Electric LC1D TeSys D Contactors_x000D_
TeSys D Contactors from Schneider Electric combine long mechanical and electrical life to offer a high reliable contactor. The range has been designed for integration in control systems and can be used to create motor starters for any type of application. The TeSys D contactors offer quick simple setup while maintaining compliance with international standards._x000D_
Features and Benefits_x000D_
Built-in auxiliary contacts for added switching capability_x000D_
Screw connections: IP20 finger-safe terminals with both North American and International terminal markings_x000D_
Can be panel mounted with screws or DIN Rail mounted_x000D_
Bidirectional peak limiting diode suppressor to protect the coil_x000D_
Easily installed accessories_x000D_
Flexible control circuit to suit a wide range of applications_x000D_
What does the utilisation category AC1 and AC3 mean for the TeSys contactors?_x000D_
Contactor utilisation categories define the current making and breaking values, based on the type of load to be controlled and the operating cycle conditions._x000D_
AC-1: This applies to all AC devices with a power factor of at least 0.95. Example of use: resistive load, heating, distribution._x000D_
AC-3: This applies to squirrel cage motors where breaking occurs while the motor is running. Example of use: all squirrel cage motors, lifts, escalators, conveyors, bucket elevators, compressors, pumps, mixers, air conditioning units._x000D_
What accessories are available?_x000D_
Auxiliary contact blocks with serrated wiping action_x000D_
Front mount dust tight auxiliary contact blocks_x000D_
Pneumatic time delay blocks_x000D_
Transient voltage surge suppressors_x000D_
Interface modules and electronic timers_x000D_
Mechanical latching blocks_x000D_
Is the TeSys D range a double break pole type contactor?_x000D_
Yes the Tesys D range uses linear translation movement that provides double breaking of the poles._x000D_
LC1D150F7 Schneider Electric LC1D TeSys D Contactor._x000D_
The Schneider Electric LC1D150F7 model is a 3 pole contactor featuring a 110 V ac operating coil, with an AC-3 full load current rating of 150 A._x000D_
TeSys D._x000D_
Motor Control and Resistive load applications._x000D_
AC 4, AC-1, AC-3 category._x000D_
Ue Rated voltage Power circuit: <= 1000 V AC 25...400 Hz, Power circuit: <= 300 V DC._x000D_
Rated current 200 A (at <= 440 V AC AC-1 for power circuit, 150 A (at <= 440 V AC AC-3 for power circuit._x000D_
Circuit Voltage 110 V ac (AC 50/60 Hz circuit)._x000D_
1 NO + 1 NC auxiliary contact._x000D_
Overvoltage category III._x000D_
Rated breaking capacity 1400 A at 440 V for power circuit conforming to IEC 60947._x000D_
Complete with a protective cover._x000D_
Plate and Rail mounting._x000D_
IP20 front face conforming to IEC 60529._x000D_
Screw Clamp Terminals._x000D_
Built-in bidirectional peak limiting diode suppressor._x000D_
Weight 2.5 kg._x000D_
Fire resistant to 850 °C conforming to IEC 60695-2-1._x000D_
Approvals_x000D_
LROS (Lloyds register of shipping), CSA, UL, GOST, DNV, CCC, GL, BV, RINA, UKCA._x000D_
Standards_x000D_
CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508, IEC 60335-1.
Наш менеджер свяжется с вами в ближайшее время