Работаем с юридическими лицами, бюджетными организациями, ИП
По вопросам приобретения товара пишите на info@west-cs.ru
Schneider Electric TeSys K Series Low Consumption Control Relays._x000D_
From Schneider Electric this is the Tesys K series of low consumption Control Relays a range of reversing and non-reversing contactors up to 5.5 kW 400/415 V. Providing excellent performance and compactness ratio with seamless integration of all applications. The control relays are available as 4 pole relays with 10 A thermally rated contacts suitable for AC or DC voltages. The Control relays available as low consumption models with built-in suppression suitable for programmable controllers._x000D_
Features._x000D_
Common options available for all ratings, 6 A, 9 A, 12 A._x000D_
Control circuits available, AC, DC, low consumption DC, silent._x000D_
Applications – 2.2 kW, 4.35 kW, in AC3 and AC4._x000D_
Connectors – Screw clamp, Faston, Spring terminals, Pins for PCB (printed circuit boards)._x000D_
Contacts with 10 A Thermal rating (suitable for use down to 17 V 5mA)._x000D_
4-Pole operation with AC or DC control circuits._x000D_
Auxiliary contacts and timer modules._x000D_
Industry, infrastructure, building._x000D_
Simple control systems._x000D_
Noise sensitive areas, disturbed mains supply, silent contactor._x000D_
CA4KN31BW3 Tesys K Control Relay 3NO + 1 NC <=690 V – 24 Vdc Low Consumption Coil._x000D_
Features and Benefits._x000D_
Product name Tesys CAK._x000D_
Control Relay._x000D_
Contactor application – Control circuit._x000D_
DC-13, AC-15._x000D_
Contacts – 3 NO + 1 NC._x000D_
Circuit type DC Low consumption._x000D_
24 V dc._x000D_
Coil – Built-in bidirectional peak limiting diode suppressor._x000D_
Mounting – rail and plate._x000D_
Screw clamp terminals._x000D_
Minimum switching voltage 17 v._x000D_
Minimum switching current 5 MA._x000D_
Height 58 mm._x000D_
Width 45 mm._x000D_
Depth 57 mm._x000D_
Net weight 0.235 kg._x000D_
Flame resistance - V1 conforming to UL 94, Requirement 2 conforming to NF F 16-101, Requirement 2 conforming to NF F 16-102._x000D_
Vibration resistance - Vibrations contactor open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6, Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6._x000D_
Shock resistance - Shocks contactor open: 10 Gn for 11 ms conforming to IEC 60068-2-27, Shocks contactor closed: 15 Gn for 11 ms conforming to IEC 60068-2-2._x000D_
Protective treatment - TC conforming to IEC 60068._x000D_
Standards_x000D_
BS 5424, IEC 60947, NF C 63-140, VDE 0660, UL, CSA, IP2x.